UATYQ20AFC3Y1 |
UATYQ25AFC3Y1 |
UATYQ30AFC3Y1 |
UATYQ45AFC3Y1 |
UATYQ50AFC3Y1 |
UATYQ55AFC3Y1 |
UATYQ65AFC3Y1 |
UATYQ75AFC3Y1 |
UATYQ90AFC3Y1 |
UATYQ100AFC3Y1 |
UATYQ115AFC3Y1 |
Cooling capacity |
Nom. |
kW |
19.5 (1) |
28.0 (1) |
30.4 (1) |
44.1 (1) |
49.2 (1) |
51.6 (1) |
63.5 (1) |
73.9 (1) |
90.3 (1) |
101.6 (1) |
106.8 (1) |
|
With 30% fresh air |
kW |
21.1 |
30.4 |
33.2 |
47.8 |
53.4 |
56.3 |
68.1 |
78.9 |
96.7 |
108.2 |
114.2 |
Heating capacity |
Nom. |
kW |
17.9 (2) |
27.0 (2) |
31.3 (2) |
46.1 (2) |
51.9 (2) |
56.3 (2) |
63.8 (2) |
76.6 (2) |
93.3 (2) |
104.5 (2) |
114.2 (2) |
Power input |
Cooling |
Nom. |
kW |
6.6 (1) |
10.0 (1) |
12.0 (1) |
17.0 (1) |
19.7 (1) |
22.5 (1) |
23.6 (1) |
29.7 (1) |
33.8 (1) |
39.0 (1) |
44.3 (1) |
|
Heating |
Nom. |
kW |
5.8 (2) |
8.00 (2) |
9.6 (2) |
14.6 (2) |
16.3 (2) |
18.1 (2) |
20.0 (2) |
25.1 (2) |
29.9 (2) |
33.2 (2) |
37.3 (2) |
EER |
2.94 (3), 3.25 (6) |
2.79 (3), 3.08 (6) |
2.54 (3), 2.82 (6) |
2.60 (3), 2.82 (6) |
2.50 (3), 2.70 (6) |
2.29 (3), 2.51 (6) |
2.69 (3), 2.82 (6) |
2.49 (3), 2.58 (6) |
2.67 (3), 2.79 (6) |
2.60 (3), 2.70 (6) |
2.41 (3), 2.51 (6) |
COP |
3.07 (3), 3.46 (6) |
3.38 (3), 3.84 (6) |
3.26 (3), 3.66 (6) |
3.15 (3), 3.44 (6) |
3.19 (3), 3.51 (6) |
3.11 (3), 3.42 (6) |
3.20 (3), 3.58 (6) |
3.05 (3), 3.26 (6) |
3.12 (3), 3.33 (6) |
3.15 (3), 3.38 (6) |
3.06 (3), 3.30 (6) |
Space cooling |
Capacity |
Pdesign |
kW |
19.5 |
28.0 |
30.4 |
44.1 |
49.2 |
51.6 |
63.5 |
73.9 |
90.3 |
101.6 |
106.8 |
Space heating (Average climate) |
Capacity |
Pdesign |
kW |
17.9 |
27.0 |
31.3 |
46.1 |
52.0 |
56.3 |
63.8 |
76.6 |
93.0 |
104.5 |
114.2 |
Evaporator |
Supply side |
Air discharge direction |
|
Frontal, Left |
Frontal, Left |
Frontal, Left |
Frontal, Left, Right, Bottom |
Frontal, Left, Right, Bottom |
Frontal, Left, Right, Bottom |
Left, Right, Bottom |
Left, Right, Bottom |
Left, Right, Bottom |
Left, Right, Bottom |
Left, Right, Bottom |
|
|
Fan |
Nominal ESP |
Pa |
300 |
300 |
300 |
300 |
300 |
300 |
300 |
300 |
300 |
300 |
300 |
|
Return side |
Fan |
Nominal ESP |
Pa |
|
|
|
300 |
300 |
300 |
300 |
300 |
300 |
200 |
300 |
|
|
Air intake direction |
|
Rear |
Rear |
Rear |
Rear, Right, Left |
Rear, Right, Left |
Rear, Right, Left |
Rear, Left, Right, Bottom |
Rear, Left, Right, Bottom |
Rear, Right, Left, Bottom |
Rear, Right, Left, Bottom |
Rear, Right, Left, Bottom |
|
|
Thermodynamic heat recovery |
|
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
|
|
|
|
|
|
Fresh air |
Standard |
|
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
|
|
Ratio |
Standard |
% |
30 |
30 |
30 |
30 |
30 |
30 |
30 |
30 |
30 |
30 |
30 |
|
|
|
In free cooling |
% |
100 |
100 |
100 |
100 |
100 |
100 |
100 |
100 |
100 |
100 |
100 |
Condenser |
Refrigerant |
Type |
|
R-410A |
R-410A |
R-410A |
R-410A |
R-410A |
R-410A |
R-410A |
R-410A |
R-410A |
R-410A |
R-410A |
|
|
GWP |
|
2,087.5 |
2,087.5 |
2,087.5 |
2,087.5 |
2,087.5 |
2,087.5 |
2,087.5 |
2,087.5 |
2,087.5 |
2,087.5 |
2,087.5 |
|
|
Charge |
TCO2Eq |
15.7 |
27.1 |
27.1 |
35.5 |
35.5 |
35.5 |
31.3 |
31.3 |
41.8 |
43.8 |
48.0 |
Dimensions |
Unit |
Height |
mm |
1,576 (6) |
2,126 (6) |
2,126 (6) |
1,799 (6) |
1,799 (6) |
1,799 (6) |
1,799 (6) |
1,799 (6) |
2,180 (6) |
2,180 (6) |
2,180 (6) |
|
|
Width |
mm |
1,828 |
1,828 |
1,828 |
3,518 |
3,518 |
3,518 |
5,660 |
5,660 |
5,660 |
5,660 |
5,660 |
|
|
Depth |
mm |
1,762 |
1,762 |
1,762 |
2,272 |
2,272 |
2,272 |
2,252 |
2,252 |
2,252 |
2,252 |
2,252 |
Weight |
Unit |
kg |
686 |
796 |
796 |
1,382 |
1,535 |
1,561 |
2,142 |
2,166 |
2,338 |
2,346 |
2,398 |
Casing |
Colour |
|
RAL 7035 |
RAL 7035 |
RAL 7035 |
RAL 7035 |
RAL 7035 |
RAL 7035 |
RAL 7035 |
RAL 7035 |
RAL 7035 |
RAL 7035 |
RAL 7035 |
Sound pressure level |
Cooling |
dBA |
60 (5) |
60 (5) |
60 (5) |
61 (5) |
63 (5) |
63 (5) |
64 (5) |
64 (5) |
65 (5) |
65 (5) |
65 (5) |
Sound power level |
Cooling |
dBA |
77 (4) |
78 (4) |
78 (4) |
79 (4) |
81 (4) |
81 (4) |
83 (4) |
83 (4) |
85 (4) |
85 (4) |
85 (4) |
Power supply |
Phase |
|
3N~ |
3N~ |
3N~ |
3N~ |
3N~ |
3N~ |
3N~ |
3N~ |
3N~ |
3N~ |
3N~ |
|
Frequency |
Hz |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
|
Voltage |
V |
400 |
400 |
400 |
400 |
400 |
400 |
400 |
400 |
400 |
400 |
400 |
Current |
Recommended fuses |
A |
25 |
32 |
40 |
63 |
80 |
80 |
100 |
100 |
125 |
125 |
160 |
Notes |
(1) - Conditions for calculation: Ambient air 27°C DB, 19°C WB; External air 35°C DB, 24°C WB. 100% recirculating air; calculated according to EN 14511/2018 |
(1) - Conditions for calculation: Ambient air 27°C DB, 19°C WB; External air 35°C DB, 24°C WB. 100% recirculating air; calculated according to EN 14511/2018 |
(1) - Conditions for calculation: Ambient air 27°C DB, 19°C WB; External air 35°C DB, 24°C WB. 100% recirculating air; calculated according to EN 14511/2018 |
(1) - Conditions for calculation: Ambient air 27°C DB, 19°C WB; External air 35°C DB, 24°C WB. 100% recirculating air; calculated according to EN 14511/2018 |
(1) - Conditions for calculation: Ambient air 27°C DB, 19°C WB; External air 35°C DB, 24°C WB. 100% recirculating air; calculated according to EN 14511/2018 |
(1) - Conditions for calculation: Ambient air 27°C DB, 19°C WB; External air 35°C DB, 24°C WB. 100% recirculating air; calculated according to EN 14511/2018 |
(1) - Conditions for calculation: Ambient air 27°C DB, 19°C WB; External air 35°C DB, 24°C WB. 100% recirculating air; calculated according to EN 14511/2018 |
(1) - Conditions for calculation: Ambient air 27°C DB, 19°C WB; External air 35°C DB, 24°C WB. 100% recirculating air; calculated according to EN 14511/2018 |
(1) - Conditions for calculation: Ambient air 27°C DB, 19°C WB; External air 35°C DB, 24°C WB. 100% recirculating air; calculated according to EN 14511/2018 |
(1) - Conditions for calculation: Ambient air 27°C DB, 19°C WB; External air 35°C DB, 24°C WB. 100% recirculating air; calculated according to EN 14511/2018 |
(1) - Conditions for calculation: Ambient air 27°C DB, 19°C WB; External air 35°C DB, 24°C WB. 100% recirculating air; calculated according to EN 14511/2018 |
|
(2) - Conditions for calculation: Ambient air 20°C DB, 15°C WB; External air 7°C DB, 6°C WB. 100% recirculating air; calculated according to EN 14511/2018 |
(2) - Conditions for calculation: Ambient air 20°C DB, 15°C WB; External air 7°C DB, 6°C WB. 100% recirculating air; calculated according to EN 14511/2018 |
(2) - Conditions for calculation: Ambient air 20°C DB, 15°C WB; External air 7°C DB, 6°C WB. 100% recirculating air; calculated according to EN 14511/2018 |
(2) - Conditions for calculation: Ambient air 20°C DB, 15°C WB; External air 7°C DB, 6°C WB. 100% recirculating air; calculated according to EN 14511/2018 |
(2) - Conditions for calculation: Ambient air 20°C DB, 15°C WB; External air 7°C DB, 6°C WB. 100% recirculating air; calculated according to EN 14511/2018 |
(2) - Conditions for calculation: Ambient air 20°C DB, 15°C WB; External air 7°C DB, 6°C WB. 100% recirculating air; calculated according to EN 14511/2018 |
(2) - Conditions for calculation: Ambient air 20°C DB, 15°C WB; External air 7°C DB, 6°C WB. 100% recirculating air; calculated according to EN 14511/2018 |
(2) - Conditions for calculation: Ambient air 20°C DB, 15°C WB; External air 7°C DB, 6°C WB. 100% recirculating air; calculated according to EN 14511/2018 |
(2) - Conditions for calculation: Ambient air 20°C DB, 15°C WB; External air 7°C DB, 6°C WB. 100% recirculating air; calculated according to EN 14511/2018 |
(2) - Conditions for calculation: Ambient air 20°C DB, 15°C WB; External air 7°C DB, 6°C WB. 100% recirculating air; calculated according to EN 14511/2018 |
(2) - Conditions for calculation: Ambient air 20°C DB, 15°C WB; External air 7°C DB, 6°C WB. 100% recirculating air; calculated according to EN 14511/2018 |
|
(3) - Calculated according to EN 14511/2018 |
(3) - Calculated according to EN 14511/2018 |
(3) - Calculated according to EN 14511/2018 |
(3) - Calculated according to EN 14511/2018 |
(3) - Calculated according to EN 14511/2018 |
(3) - Calculated according to EN 14511/2018 |
(3) - Calculated according to EN 14511/2018 |
(3) - Calculated according to EN 14511/2018 |
(3) - Calculated according to EN 14511/2018 |
(3) - Calculated according to EN 14511/2018 |
(3) - Calculated according to EN 14511/2018 |
|
(4) - Sound power level in free field calculated according to standard ISO 3744. Values refer only to the base unit version |
(4) - Sound power level in free field calculated according to standard ISO 3744. Values refer only to the base unit version |
(4) - Sound power level in free field calculated according to standard ISO 3744. Values refer only to the base unit version |
(4) - Sound power level in free field calculated according to standard ISO 3744. Values refer only to the base unit version |
(4) - Sound power level in free field calculated according to standard ISO 3744. Values refer only to the base unit version |
(4) - Sound power level in free field calculated according to standard ISO 3744. Values refer only to the base unit version |
(4) - Sound power level in free field calculated according to standard ISO 3744. Values refer only to the base unit version |
(4) - Sound power level in free field calculated according to standard ISO 3744. Values refer only to the base unit version |
(4) - Sound power level in free field calculated according to standard ISO 3744. Values refer only to the base unit version |
(4) - Sound power level in free field calculated according to standard ISO 3744. Values refer only to the base unit version |
(4) - Sound power level in free field calculated according to standard ISO 3744. Values refer only to the base unit version |
|
(5) - Average Sound Pressure Level at 1 meter in free field on a reflecting surface |
(5) - Average Sound Pressure Level at 1 meter in free field on a reflecting surface |
(5) - Average Sound Pressure Level at 1 meter in free field on a reflecting surface |
(5) - Average Sound Pressure Level at 1 meter in free field on a reflecting surface |
(5) - Average Sound Pressure Level at 1 meter in free field on a reflecting surface |
(5) - Average Sound Pressure Level at 1 meter in free field on a reflecting surface |
(5) - Average Sound Pressure Level at 1 meter in free field on a reflecting surface |
(5) - Average Sound Pressure Level at 1 meter in free field on a reflecting surface |
(5) - Average Sound Pressure Level at 1 meter in free field on a reflecting surface |
(5) - Average Sound Pressure Level at 1 meter in free field on a reflecting surface |
(5) - Average Sound Pressure Level at 1 meter in free field on a reflecting surface |
|
(6) - Maximum external unit dimensions without pallet |
(6) - Maximum external unit dimensions without pallet |
(6) - Maximum external unit dimensions without pallet |
(6) - Maximum external unit dimensions without pallet |
(6) - Maximum external unit dimensions without pallet |
(6) - Maximum external unit dimensions without pallet |
(6) - Maximum external unit dimensions without pallet |
(6) - Maximum external unit dimensions without pallet |
(6) - Maximum external unit dimensions without pallet |
(6) - Maximum external unit dimensions without pallet |
(6) - Maximum external unit dimensions without pallet |