|
RWEYQ8T9Y1B |
RWEYQ10T9Y1B |
RWEYQ12T9Y1B |
RWEYQ14T9Y1B |
RWEYQ16T9Y1B |
RWEYQ18T9Y1B |
RWEYQ20T9Y1B |
RWEYQ24T9Y1B |
RWEYQ26T9Y1B |
RWEYQ28T9Y1B |
RWEYQ22T9Y1B |
RWEYQ30T9Y1B |
RWEYQ32T9Y1B |
RWEYQ34T9Y1B |
RWEYQ36T9Y1B |
RWEYQ38T9Y1B |
RWEYQ40T9Y1B |
RWEYQ42T9Y1B |
System |
Outdoor unit module 1 |
|
|
|
|
RWEYQ8T |
RWEYQ8T |
RWEYQ10T |
RWEYQ12T |
RWEYQ12T |
RWEYQ14T |
RWEYQ10T |
RWEYQ10T |
RWEYQ10T |
RWEYQ10T |
RWEYQ12T |
RWEYQ12T |
RWEYQ12T |
RWEYQ14T |
|
Outdoor unit module 2 |
|
|
|
|
RWEYQ8T |
RWEYQ10T |
RWEYQ10T |
RWEYQ12T |
RWEYQ14T |
RWEYQ14T |
RWEYQ12T |
RWEYQ10T |
RWEYQ10T |
RWEYQ12T |
RWEYQ12T |
RWEYQ12T |
RWEYQ14T |
RWEYQ14T |
|
Outdoor unit module 3 |
|
|
|
|
|
|
|
|
|
|
|
RWEYQ10T |
RWEYQ12T |
RWEYQ12T |
RWEYQ12T |
RWEYQ14T |
RWEYQ14T |
RWEYQ14T |
Recommended combination |
4 x FXMQ50P7VEB |
4 x FXMQ63P7VEB |
6 x FXMQ50P7VEB |
1 x FXMQ50P7VEB + 5 x FXMQ63P7VEB |
4 x FXMQ63P7VEB + 2 x FXMQ80P7VEB |
4 x FXMQ50P7VEB + 4 x FXMQ63P7VEB |
8 x FXMQ63P7VEB |
12 x FXMQ50P7VEB |
7 x FXMQ50P7VEB + 5 x FXMQ63P7VEB |
2 x FXMQ50P7VEB + 10 x FXMQ63P7VEB |
6 x FXMQ50P7VEB + 4 x FXMQ63P7VEB |
12 x FXMQ63P7VEB |
6 x FXMQ50P7VEB + 8 x FXMQ63P7VEB |
12 x FXMQ50P7VEB + 4 x FXMQ63P7VEB |
18 x FXMQ50P7VEB |
13 x FXMQ50P7VEB + 5 x FXMQ63P7VEB |
8 x FXMQ50P7VEB + 10 x FXMQ63P7VEB |
3 x FXMQ50P7VEB + 15 x FXMQ63P7VEB |
Cooling capacity |
Prated,c |
kW |
22.4 (1) |
28.0 (1) |
33.5 (1) |
40.0 (1) |
44.8 (1) |
50.4 (1) |
56.0 (1) |
67.0 (1) |
73.5 (1) |
80.0 (1) |
61.5 (1) |
84.0 (1) |
89.5 (1) |
95.0 (1) |
100.5 (1) |
107.0 (1) |
113.5 (1) |
120.0 (1) |
|
Nom. |
30°C inlet water temp. ID27/19 AHRI |
Nom. Waterflow |
Btu/h |
73,000 (4) |
92,000 (4) |
110,000 (4) |
131,000 (5) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Nom. Waterflow |
kW |
21.30 (4) |
27.00 (4) |
32.10 (4) |
38.40 (5) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
30°C inlet water temp. ID27/19 ISO |
Nom. Waterflow |
Btu/h |
73,430 (2) |
92,080 (2) |
109,480 (2) |
131,510 (3) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Nom. Waterflow |
kW |
21.51 (2) |
26.99 (2) |
32.09 (2) |
38.54 (3) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Heating capacity |
Prated,h |
kW |
25.0 |
31.5 |
37.5 |
45.0 |
50.0 |
56.5 |
62.5 |
75.0 |
82.5 |
90.0 |
69.0 |
94.5 |
100.5 |
106.5 |
112.5 |
120.0 |
127.5 |
135.0 |
Power input - 50Hz |
Cooling |
Nom. |
30°C inlet water temp. ID27/19 AHRI |
kW |
4.52 (4) |
5.59 (4) |
7.59 (4) |
9.01 (5) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
30°C inlet water temp. ID27/19 ISO |
kW |
4.45 (2) |
5.47 (2) |
7.45 (2) |
8.96 (3) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
EER at nom. capacity |
30°C inlet water temp. ID27/19 AHRI |
Nom. Waterflow |
Btu/h/W |
16.10 (4) |
16.50 (4) |
14.50 (4) |
14.50 (5) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Nom. Waterflow |
kW/kW |
4.71 (4) |
4.83 (4) |
4.23 (4) |
4.26 (5) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
30°C inlet water temp. ID27/19 ISO |
Nom. Waterflow |
Btu/h/W |
16.49 (2) |
16.83 (2) |
14.71 (2) |
14.69 (3) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Nom. Waterflow |
kW/kW |
4.83 (2) |
4.93 (2) |
4.31 (2) |
4.30 (3) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
SCOP |
13.3 |
11.8 |
11.1 |
10.1 |
11.7 |
12.5 |
11.9 |
11.1 |
10.4 |
9.9 |
11.4 |
11.9 |
11.6 |
11.4 |
11.2 |
10.7 |
10.3 |
10.0 |
SEER |
8.4 |
7.9 |
9.2 |
8.5 |
7.9 |
7.9 |
7.7 |
8.8 |
8.3 |
7.9 |
8.0 |
7.9 |
8.2 |
8.8 |
9.0 |
8.7 |
8.7 |
8.5 |
Space cooling |
A Condition (35°C - 27/19), cooling tower (inlet/outlet) 30/35 |
EERd |
% |
5.6 |
4.6 |
5.4 |
4.2 |
5.1 |
5.0 |
4.6 |
5.4 |
4.9 |
4.5 |
5.0 |
4.6 |
4.9 |
5.1 |
5.4 |
5.0 |
4.7 |
4.5 |
|
|
Pdc |
kW |
22.4 |
28.0 |
33.5 |
40.0 |
44.8 |
50.4 |
56.0 |
67.0 |
73.5 |
80.0 |
61.5 |
84.0 |
89.5 |
95.0 |
100.5 |
107.0 |
113.5 |
120.0 |
|
B Condition (30°C - 27/19), cooling tower (inlet/outlet) 26/* |
EERd |
% |
6.9 |
6.3 |
7.0 |
6.3 |
6.5 |
6.5 |
6.3 |
7.0 |
6.6 |
6.3 |
6.6 |
6.3 |
6.5 |
6.7 |
7.0 |
6.7 |
6.5 |
6.3 |
|
|
Pdc |
kW |
16.5 |
20.6 |
24.7 |
29.5 |
33.0 |
37.1 |
41.3 |
49.4 |
54.2 |
58.9 |
45.3 |
61.9 |
66.0 |
70.0 |
74.1 |
78.8 |
83.6 |
88.4 |
|
C Condition (25°C - 27/19), cooling tower (inlet/outlet) 22/* |
EERd |
% |
10.1 |
9.1 |
10.5 |
9.4 |
9.0 |
9.5 |
9.1 |
10.5 |
9.9 |
9.4 |
9.8 |
9.1 |
9.6 |
10.1 |
10.5 |
10.1 |
9.7 |
9.4 |
|
|
Pdc |
kW |
10.6 |
13.3 |
15.9 |
18.9 |
21.2 |
23.9 |
26.5 |
31.7 |
34.8 |
37.9 |
29.1 |
39.8 |
42.4 |
45.0 |
47.6 |
50.7 |
53.8 |
56.8 |
|
D Condition (20°C - 27/19), cooling tower (inlet/outlet) 18/* |
EERd |
% |
11.9 |
12.3 |
14.9 |
15.6 |
11.0 |
10.1 |
9.9 |
11.5 |
10.8 |
10.2 |
9.4 |
11.6 |
11.2 |
13.5 |
13.1 |
12.8 |
15.4 |
15.4 |
|
|
Pdc |
kW |
7.9 |
7.9 |
8.2 |
8.4 |
9.4 |
10.6 |
11.8 |
14.1 |
15.5 |
16.8 |
13.0 |
17.7 |
18.8 |
20.0 |
21.2 |
22.5 |
24.5 |
25.3 |
Space heating (Average climate) |
TBivalent |
COPd (declared COP) |
|
7.2 |
6.1 |
5.8 |
5.8 |
6.1 |
6.6 |
6.2 |
5.8 |
5.3 |
4.9 |
6.0 |
6.2 |
6.1 |
5.9 |
5.8 |
5.4 |
5.1 |
4.9 |
|
|
Pdh (declared heating cap) |
kW |
25.0 |
31.5 |
37.5 |
45.0 |
50.0 |
56.5 |
63.0 |
75.0 |
82.5 |
90.0 |
69.0 |
94.5 |
100.5 |
106.5 |
112.5 |
120.0 |
127.5 |
135.0 |
|
|
Tbiv (bivalent temperature) |
°C |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
|
TOL |
COPd (declared COP) |
|
7.2 |
6.1 |
5.8 |
5.8 |
6.1 |
6.6 |
6.2 |
5.8 |
5.3 |
4.9 |
6.0 |
6.2 |
6.1 |
5.9 |
5.8 |
5.4 |
5.1 |
4.9 |
|
|
Pdh (declared heating cap) |
kW |
25.0 |
31.5 |
37.5 |
45.0 |
50.0 |
56.5 |
63.0 |
75.0 |
82.5 |
90.0 |
69.0 |
94.5 |
100.5 |
106.5 |
112.5 |
120.0 |
127.5 |
135.0 |
|
|
Tol (temperature operating limit) |
°C |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
-10 |
|
A Condition (-7°C) |
COPd (declared COP) |
|
8.1 |
7.1 |
6.6 |
5.8 |
6.9 |
7.5 |
7.1 |
6.6 |
6.1 |
5.7 |
6.8 |
7.1 |
6.9 |
6.7 |
6.6 |
6.3 |
6.0 |
5.7 |
|
|
Pdh (declared heating cap) |
kW |
22.1 |
27.9 |
33.2 |
39.6 |
44.2 |
50.0 |
55.7 |
66.3 |
73.0 |
79.6 |
61.0 |
83.6 |
88.9 |
94.2 |
99.5 |
106.2 |
112.8 |
119.4 |
|
B Condition (2°C) |
COPd (declared COP) |
|
13.0 |
11.4 |
10.7 |
9.5 |
11.4 |
12.1 |
11.4 |
10.7 |
10.0 |
9.5 |
11.0 |
11.4 |
11.1 |
10.9 |
10.7 |
10.2 |
9.8 |
9.5 |
|
|
Pdh (declared heating cap) |
kW |
13.5 |
17.0 |
20.2 |
24.3 |
26.9 |
30.4 |
33.9 |
40.4 |
44.4 |
48.5 |
37.2 |
50.9 |
54.1 |
57.3 |
60.6 |
64.6 |
68.6 |
72.7 |
|
C Condition (7°C) |
COPd (declared COP) |
|
19.1 |
16.8 |
15.5 |
14.3 |
16.3 |
17.8 |
16.8 |
15.5 |
14.8 |
14.3 |
16.1 |
16.8 |
16.3 |
15.9 |
15.5 |
15.0 |
14.6 |
14.3 |
|
|
Pdh (declared heating cap) |
kW |
8.9 |
10.9 |
13.0 |
15.8 |
17.5 |
19.8 |
21.8 |
26.0 |
28.6 |
31.2 |
23.9 |
32.7 |
34.8 |
36.9 |
38.9 |
41.5 |
44.1 |
46.7 |
|
D Condition (12°C) |
COPd (declared COP) |
|
19.1 |
20.1 |
19.3 |
23.8 |
17.8 |
17.7 |
18.3 |
16.7 |
15.8 |
16.0 |
17.0 |
19.4 |
19.4 |
19.3 |
19.3 |
18.8 |
18.9 |
18.4 |
|
|
Pdh (declared heating cap) |
kW |
8.9 |
8.8 |
8.8 |
9.2 |
8.6 |
8.7 |
9.6 |
11.5 |
12.7 |
13.9 |
10.6 |
17.7 |
17.7 |
17.6 |
17.6 |
18.5 |
19.6 |
20.8 |
Capacity range |
HP |
8 |
10 |
12 |
14 |
16 |
18 |
20 |
24 |
26 |
28 |
22 |
30 |
32 |
34 |
36 |
38 |
40 |
42 |
Maximum number of connectable indoor units |
64 (7) |
64 (7) |
64 (7) |
64 (7) |
64 (7) |
64 (7) |
64 (7) |
64 (7) |
64 (7) |
64 (7) |
64 (7) |
64 (7) |
64 (7) |
64 (7) |
64 (7) |
64 (7) |
64 (7) |
64 (7) |
Indoor index connection |
Min. |
|
100.0 |
125.0 |
150.0 |
175.0 |
200.0 |
225.0 |
250.0 |
300.0 |
325.0 |
350.0 |
275.0 |
375.0 |
400.0 |
425.0 |
450.0 |
475.0 |
500.0 |
525.0 |
|
Max. |
|
300.0 |
375.0 |
450.0 |
525.0 |
600.0 |
675.0 |
750.0 |
900.0 |
975.0 |
1,050.0 |
825.0 |
1,125.0 |
1,200.0 |
1,275.0 |
1,350.0 |
1,425.0 |
1,500.0 |
1,575.0 |
Димензии |
Unit |
Height |
mm |
980 |
980 |
980 |
980 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Width |
mm |
767 |
767 |
767 |
767 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Depth |
mm |
560 |
560 |
560 |
560 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Weight |
Unit |
kg |
195 |
195 |
197 |
197 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Compressor |
Type |
|
Hermetically sealed scroll inverter compressor |
Hermetically sealed scroll inverter compressor |
Hermetically sealed scroll inverter compressor |
Hermetically sealed scroll inverter compressor |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Sound power level |
Cooling |
Nom. |
dBA |
65.0 (9) |
71.0 (9) |
72.0 (9) |
74.0 (9) |
68.0 (9) |
72.0 (9) |
74.0 (9) |
75.0 (9) |
76.0 (9) |
77.0 (9) |
75.0 (9) |
76.0 (9) |
76.0 (9) |
76.0 (9) |
77.0 (9) |
78.0 (9) |
78.0 (9) |
79.0 (9) |
Sound pressure level |
Cooling |
Nom. |
dBA |
48.0 (10) |
50.0 (10) |
56.0 (10) |
58.0 (10) |
51.0 (10) |
52.0 (10) |
53.0 (10) |
59.0 (10) |
60.0 (10) |
61.0 (10) |
57.0 (10) |
55.0 (10) |
58.0 (10) |
60.0 (10) |
61.0 (10) |
62.0 (10) |
62.0 (10) |
63.0 (10) |
Refrigerant |
Type |
|
R-410A |
R-410A |
R-410A |
R-410A |
R-410A |
R-410A |
R-410A |
R-410A |
R-410A |
R-410A |
R-410A |
R-410A |
R-410A |
R-410A |
R-410A |
R-410A |
R-410A |
R-410A |
|
GWP |
|
2,087.5 |
2,087.5 |
2,087.5 |
2,087.5 |
2,087.5 |
2,087.5 |
2,087.5 |
2,087.5 |
2,087.5 |
2,087.5 |
2,087.5 |
2,087.5 |
2,087.5 |
2,087.5 |
2,087.5 |
2,087.5 |
2,087.5 |
2,087.5 |
|
Charge |
kg |
7.9 |
7.9 |
9.6 |
9.6 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Charge |
TCO2Eq |
16.5 |
16.5 |
20.0 |
20.0 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Piping connections |
Течност |
Type |
|
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
|
|
OD |
mm |
9.52 |
9.52 |
12.7 |
12.7 |
12.7 |
15.9 |
15.9 |
15.9 |
19.1 |
19.1 |
15.9 |
19.1 |
19.1 |
19.1 |
19.1 |
19.1 |
19.1 |
19.1 |
|
Gas |
Type |
|
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
Braze connection |
|
|
OD |
mm |
19.1 (11) |
22.2 (11) |
28.6 (11) |
28.6 (11) |
28.6 (11) |
28.6 (11) |
28.6 (11) |
34.9 (11) |
34.9 (11) |
34.9 (11) |
28.6 (11) |
34.9 (11) |
34.9 (11) |
34.9 (11) |
41.3 (11) |
41.3 (11) |
41.3 (11) |
41.3 (11) |
|
HP/LP gas |
OD |
mm |
15.9 (12), 19.1 (13) |
19.1 (12), 22.2 (13) |
19.1 (12), 28.6 (13) |
22.2 (12), 28.6 (13) |
22.2 (12), 28.6 (13) |
22.2 (12), 28.6 (13) |
28.6 (12), 28.6 (13) |
28.6 (12), 34.9 (13) |
28.6 (12), 34.9 (13) |
28.6 (12), 34.9 (13) |
28.6 (12), 28.6 (13) |
28.6 (12), 34.9 (13) |
28.6 (12), 34.9 (13) |
28.6 (12), 34.9 (13) |
28.6 (12), 41.3 (13) |
41.3 (13), 34.9 (12) |
41.3 (13), 34.9 (12) |
41.3 (13), 34.9 (12) |
|
Total piping length |
System |
Actual |
m |
500 (14) |
500 (14) |
500 (14) |
500 (14) |
500 (14) |
500 (14) |
500 (14) |
500 (14) |
500 (14) |
500 (14) |
500 (14) |
500 (14) |
500 (14) |
500 (14) |
500 (14) |
500 (14) |
500 (14) |
500 (14) |
Standard Accessories |
Прирачник за инсталирање |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
|
Прирачник за работа |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
|
Цевки за поврзување |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
|
Цевки за довод на вода со филтер |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
Power supply |
Name |
|
Y1 |
Y1 |
Y1 |
Y1 |
Y1 |
Y1 |
Y1 |
Y1 |
Y1 |
Y1 |
Y1 |
Y1 |
Y1 |
Y1 |
Y1 |
Y1 |
Y1 |
Y1 |
|
Phase |
|
3N~ |
3N~ |
3N~ |
3N~ |
3N~ |
3N~ |
3N~ |
3N~ |
3N~ |
3N~ |
3N~ |
3N~ |
3N~ |
3N~ |
3N~ |
3N~ |
3N~ |
3N~ |
|
Frequency |
Hz |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
|
Voltage |
V |
380-415 |
380-415 |
380-415 |
380-415 |
380-415 |
380-415 |
380-415 |
380-415 |
380-415 |
380-415 |
380-415 |
380-415 |
380-415 |
380-415 |
380-415 |
380-415 |
380-415 |
380-415 |
Notes |
(1) - Cooling: indoor temp. 27°CDB, 19°CWB; Inlet water temperature: 30°C; equivalent refrigerant piping: 7.5m; level difference: 0m. |
(1) - Cooling: indoor temp. 27°CDB, 19°CWB; Inlet water temperature: 30°C; equivalent refrigerant piping: 7.5m; level difference: 0m. |
(1) - Cooling: indoor temp. 27°CDB, 19°CWB; Inlet water temperature: 30°C; equivalent refrigerant piping: 7.5m; level difference: 0m. |
(1) - Cooling: indoor temp. 27°CDB, 19°CWB; Inlet water temperature: 30°C; equivalent refrigerant piping: 7.5m; level difference: 0m. |
(1) - Cooling: indoor temp. 27°CDB, 19°CWB; Inlet water temperature: 30°C; equivalent refrigerant piping: 7.5m; level difference: 0m. |
(1) - Cooling: indoor temp. 27°CDB, 19°CWB; Inlet water temperature: 30°C; equivalent refrigerant piping: 7.5m; level difference: 0m. |
(1) - Cooling: indoor temp. 27°CDB, 19°CWB; Inlet water temperature: 30°C; equivalent refrigerant piping: 7.5m; level difference: 0m. |
(1) - Cooling: indoor temp. 27°CDB, 19°CWB; Inlet water temperature: 30°C; equivalent refrigerant piping: 7.5m; level difference: 0m. |
(1) - Cooling: indoor temp. 27°CDB, 19°CWB; Inlet water temperature: 30°C; equivalent refrigerant piping: 7.5m; level difference: 0m. |
(1) - Cooling: indoor temp. 27°CDB, 19°CWB; Inlet water temperature: 30°C; equivalent refrigerant piping: 7.5m; level difference: 0m. |
(1) - Cooling: indoor temp. 27°CDB, 19°CWB; Inlet water temperature: 30°C; equivalent refrigerant piping: 7.5m; level difference: 0m. |
(1) - Cooling: indoor temp. 27°CDB, 19°CWB; Inlet water temperature: 30°C; equivalent refrigerant piping: 7.5m; level difference: 0m. |
(1) - Cooling: indoor temp. 27°CDB, 19°CWB; Inlet water temperature: 30°C; equivalent refrigerant piping: 7.5m; level difference: 0m. |
(1) - Cooling: indoor temp. 27°CDB, 19°CWB; Inlet water temperature: 30°C; equivalent refrigerant piping: 7.5m; level difference: 0m. |
(1) - Cooling: indoor temp. 27°CDB, 19°CWB; Inlet water temperature: 30°C; equivalent refrigerant piping: 7.5m; level difference: 0m. |
(1) - Cooling: indoor temp. 27°CDB, 19°CWB; Inlet water temperature: 30°C; equivalent refrigerant piping: 7.5m; level difference: 0m. |
(1) - Cooling: indoor temp. 27°CDB, 19°CWB; Inlet water temperature: 30°C; equivalent refrigerant piping: 7.5m; level difference: 0m. |
(1) - Cooling: indoor temp. 27°CDB, 19°CWB; Inlet water temperature: 30°C; equivalent refrigerant piping: 7.5m; level difference: 0m. |
|
(2) - Cooling T3: Indoor temp 29°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,6m Level difference piping 0m Power input indoors included According to teststandard ISO 13256: 1998 |
(2) - Cooling T3: Indoor temp 29°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,6m Level difference piping 0m Power input indoors included According to teststandard ISO 13256: 1998 |
(2) - Cooling T3: Indoor temp 29°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,6m Level difference piping 0m Power input indoors included According to teststandard ISO 13256: 1998 |
(2) - Cooling T3: Indoor temp 29°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,6m Level difference piping 0m Power input indoors included According to teststandard ISO 13256: 1998 |
(2) - Cooling T3: Indoor temp 29°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,6m Level difference piping 0m Power input indoors included According to teststandard ISO 13256: 1998 |
(2) - Cooling T3: Indoor temp 29°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,6m Level difference piping 0m Power input indoors included According to teststandard ISO 13256: 1998 |
(2) - Cooling T3: Indoor temp 29°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,6m Level difference piping 0m Power input indoors included According to teststandard ISO 13256: 1998 |
(2) - Cooling T3: Indoor temp 29°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,6m Level difference piping 0m Power input indoors included According to teststandard ISO 13256: 1998 |
(2) - Cooling T3: Indoor temp 29°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,6m Level difference piping 0m Power input indoors included According to teststandard ISO 13256: 1998 |
(2) - Cooling T3: Indoor temp 29°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,6m Level difference piping 0m Power input indoors included According to teststandard ISO 13256: 1998 |
(2) - Cooling T3: Indoor temp 29°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,6m Level difference piping 0m Power input indoors included According to teststandard ISO 13256: 1998 |
(2) - Cooling T3: Indoor temp 29°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,6m Level difference piping 0m Power input indoors included According to teststandard ISO 13256: 1998 |
(2) - Cooling T3: Indoor temp 29°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,6m Level difference piping 0m Power input indoors included According to teststandard ISO 13256: 1998 |
(2) - Cooling T3: Indoor temp 29°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,6m Level difference piping 0m Power input indoors included According to teststandard ISO 13256: 1998 |
(2) - Cooling T3: Indoor temp 29°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,6m Level difference piping 0m Power input indoors included According to teststandard ISO 13256: 1998 |
(2) - Cooling T3: Indoor temp 29°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,6m Level difference piping 0m Power input indoors included According to teststandard ISO 13256: 1998 |
(2) - Cooling T3: Indoor temp 29°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,6m Level difference piping 0m Power input indoors included According to teststandard ISO 13256: 1998 |
(2) - Cooling T3: Indoor temp 29°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,6m Level difference piping 0m Power input indoors included According to teststandard ISO 13256: 1998 |
|
(3) - Cooling T3: Indoor temp 29°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,5m Level difference piping 0m Power input indoors included According to teststandard ISO 13256: 1998 |
(3) - Cooling T3: Indoor temp 29°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,5m Level difference piping 0m Power input indoors included According to teststandard ISO 13256: 1998 |
(3) - Cooling T3: Indoor temp 29°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,5m Level difference piping 0m Power input indoors included According to teststandard ISO 13256: 1998 |
(3) - Cooling T3: Indoor temp 29°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,5m Level difference piping 0m Power input indoors included According to teststandard ISO 13256: 1998 |
(3) - Cooling T3: Indoor temp 29°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,5m Level difference piping 0m Power input indoors included According to teststandard ISO 13256: 1998 |
(3) - Cooling T3: Indoor temp 29°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,5m Level difference piping 0m Power input indoors included According to teststandard ISO 13256: 1998 |
(3) - Cooling T3: Indoor temp 29°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,5m Level difference piping 0m Power input indoors included According to teststandard ISO 13256: 1998 |
(3) - Cooling T3: Indoor temp 29°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,5m Level difference piping 0m Power input indoors included According to teststandard ISO 13256: 1998 |
(3) - Cooling T3: Indoor temp 29°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,5m Level difference piping 0m Power input indoors included According to teststandard ISO 13256: 1998 |
(3) - Cooling T3: Indoor temp 29°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,5m Level difference piping 0m Power input indoors included According to teststandard ISO 13256: 1998 |
(3) - Cooling T3: Indoor temp 29°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,5m Level difference piping 0m Power input indoors included According to teststandard ISO 13256: 1998 |
(3) - Cooling T3: Indoor temp 29°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,5m Level difference piping 0m Power input indoors included According to teststandard ISO 13256: 1998 |
(3) - Cooling T3: Indoor temp 29°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,5m Level difference piping 0m Power input indoors included According to teststandard ISO 13256: 1998 |
(3) - Cooling T3: Indoor temp 29°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,5m Level difference piping 0m Power input indoors included According to teststandard ISO 13256: 1998 |
(3) - Cooling T3: Indoor temp 29°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,5m Level difference piping 0m Power input indoors included According to teststandard ISO 13256: 1998 |
(3) - Cooling T3: Indoor temp 29°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,5m Level difference piping 0m Power input indoors included According to teststandard ISO 13256: 1998 |
(3) - Cooling T3: Indoor temp 29°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,5m Level difference piping 0m Power input indoors included According to teststandard ISO 13256: 1998 |
(3) - Cooling T3: Indoor temp 29°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,5m Level difference piping 0m Power input indoors included According to teststandard ISO 13256: 1998 |
|
(4) - Cooling T1: Indoor temp 27°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,6m Level difference piping 0m Power input indoors included According to teststandard AHRI 1230: 2010 |
(4) - Cooling T1: Indoor temp 27°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,6m Level difference piping 0m Power input indoors included According to teststandard AHRI 1230: 2010 |
(4) - Cooling T1: Indoor temp 27°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,6m Level difference piping 0m Power input indoors included According to teststandard AHRI 1230: 2010 |
(4) - Cooling T1: Indoor temp 27°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,6m Level difference piping 0m Power input indoors included According to teststandard AHRI 1230: 2010 |
(4) - Cooling T1: Indoor temp 27°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,6m Level difference piping 0m Power input indoors included According to teststandard AHRI 1230: 2010 |
(4) - Cooling T1: Indoor temp 27°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,6m Level difference piping 0m Power input indoors included According to teststandard AHRI 1230: 2010 |
(4) - Cooling T1: Indoor temp 27°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,6m Level difference piping 0m Power input indoors included According to teststandard AHRI 1230: 2010 |
(4) - Cooling T1: Indoor temp 27°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,6m Level difference piping 0m Power input indoors included According to teststandard AHRI 1230: 2010 |
(4) - Cooling T1: Indoor temp 27°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,6m Level difference piping 0m Power input indoors included According to teststandard AHRI 1230: 2010 |
(4) - Cooling T1: Indoor temp 27°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,6m Level difference piping 0m Power input indoors included According to teststandard AHRI 1230: 2010 |
(4) - Cooling T1: Indoor temp 27°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,6m Level difference piping 0m Power input indoors included According to teststandard AHRI 1230: 2010 |
(4) - Cooling T1: Indoor temp 27°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,6m Level difference piping 0m Power input indoors included According to teststandard AHRI 1230: 2010 |
(4) - Cooling T1: Indoor temp 27°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,6m Level difference piping 0m Power input indoors included According to teststandard AHRI 1230: 2010 |
(4) - Cooling T1: Indoor temp 27°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,6m Level difference piping 0m Power input indoors included According to teststandard AHRI 1230: 2010 |
(4) - Cooling T1: Indoor temp 27°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,6m Level difference piping 0m Power input indoors included According to teststandard AHRI 1230: 2010 |
(4) - Cooling T1: Indoor temp 27°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,6m Level difference piping 0m Power input indoors included According to teststandard AHRI 1230: 2010 |
(4) - Cooling T1: Indoor temp 27°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,6m Level difference piping 0m Power input indoors included According to teststandard AHRI 1230: 2010 |
(4) - Cooling T1: Indoor temp 27°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 7,6m Level difference piping 0m Power input indoors included According to teststandard AHRI 1230: 2010 |
|
(5) - Cooling T1: Indoor temp 27°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 15,5m Level difference piping 0m Power input indoors included According to teststandard AHRI 1230: 2010 |
(5) - Cooling T1: Indoor temp 27°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 15,5m Level difference piping 0m Power input indoors included According to teststandard AHRI 1230: 2010 |
(5) - Cooling T1: Indoor temp 27°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 15,5m Level difference piping 0m Power input indoors included According to teststandard AHRI 1230: 2010 |
(5) - Cooling T1: Indoor temp 27°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 15,5m Level difference piping 0m Power input indoors included According to teststandard AHRI 1230: 2010 |
(5) - Cooling T1: Indoor temp 27°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 15,5m Level difference piping 0m Power input indoors included According to teststandard AHRI 1230: 2010 |
(5) - Cooling T1: Indoor temp 27°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 15,5m Level difference piping 0m Power input indoors included According to teststandard AHRI 1230: 2010 |
(5) - Cooling T1: Indoor temp 27°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 15,5m Level difference piping 0m Power input indoors included According to teststandard AHRI 1230: 2010 |
(5) - Cooling T1: Indoor temp 27°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 15,5m Level difference piping 0m Power input indoors included According to teststandard AHRI 1230: 2010 |
(5) - Cooling T1: Indoor temp 27°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 15,5m Level difference piping 0m Power input indoors included According to teststandard AHRI 1230: 2010 |
(5) - Cooling T1: Indoor temp 27°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 15,5m Level difference piping 0m Power input indoors included According to teststandard AHRI 1230: 2010 |
(5) - Cooling T1: Indoor temp 27°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 15,5m Level difference piping 0m Power input indoors included According to teststandard AHRI 1230: 2010 |
(5) - Cooling T1: Indoor temp 27°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 15,5m Level difference piping 0m Power input indoors included According to teststandard AHRI 1230: 2010 |
(5) - Cooling T1: Indoor temp 27°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 15,5m Level difference piping 0m Power input indoors included According to teststandard AHRI 1230: 2010 |
(5) - Cooling T1: Indoor temp 27°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 15,5m Level difference piping 0m Power input indoors included According to teststandard AHRI 1230: 2010 |
(5) - Cooling T1: Indoor temp 27°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 15,5m Level difference piping 0m Power input indoors included According to teststandard AHRI 1230: 2010 |
(5) - Cooling T1: Indoor temp 27°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 15,5m Level difference piping 0m Power input indoors included According to teststandard AHRI 1230: 2010 |
(5) - Cooling T1: Indoor temp 27°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 15,5m Level difference piping 0m Power input indoors included According to teststandard AHRI 1230: 2010 |
(5) - Cooling T1: Indoor temp 27°CDB/19°CWB Water inlet temp 30°C Nom. waterflow Equivalent piping length 15,5m Level difference piping 0m Power input indoors included According to teststandard AHRI 1230: 2010 |
|
(6) - Heating: indoor temp. 20°CDB; inlet water temperature: 20°C; equivalent piping length: 7.5m; level difference: 0m |
(6) - Heating: indoor temp. 20°CDB; inlet water temperature: 20°C; equivalent piping length: 7.5m; level difference: 0m |
(6) - Heating: indoor temp. 20°CDB; inlet water temperature: 20°C; equivalent piping length: 7.5m; level difference: 0m |
(6) - Heating: indoor temp. 20°CDB; inlet water temperature: 20°C; equivalent piping length: 7.5m; level difference: 0m |
(6) - Heating: indoor temp. 20°CDB; inlet water temperature: 20°C; equivalent piping length: 7.5m; level difference: 0m |
(6) - Heating: indoor temp. 20°CDB; inlet water temperature: 20°C; equivalent piping length: 7.5m; level difference: 0m |
(6) - Heating: indoor temp. 20°CDB; inlet water temperature: 20°C; equivalent piping length: 7.5m; level difference: 0m |
(6) - Heating: indoor temp. 20°CDB; inlet water temperature: 20°C; equivalent piping length: 7.5m; level difference: 0m |
(6) - Heating: indoor temp. 20°CDB; inlet water temperature: 20°C; equivalent piping length: 7.5m; level difference: 0m |
(6) - Heating: indoor temp. 20°CDB; inlet water temperature: 20°C; equivalent piping length: 7.5m; level difference: 0m |
(6) - Heating: indoor temp. 20°CDB; inlet water temperature: 20°C; equivalent piping length: 7.5m; level difference: 0m |
(6) - Heating: indoor temp. 20°CDB; inlet water temperature: 20°C; equivalent piping length: 7.5m; level difference: 0m |
(6) - Heating: indoor temp. 20°CDB; inlet water temperature: 20°C; equivalent piping length: 7.5m; level difference: 0m |
(6) - Heating: indoor temp. 20°CDB; inlet water temperature: 20°C; equivalent piping length: 7.5m; level difference: 0m |
(6) - Heating: indoor temp. 20°CDB; inlet water temperature: 20°C; equivalent piping length: 7.5m; level difference: 0m |
(6) - Heating: indoor temp. 20°CDB; inlet water temperature: 20°C; equivalent piping length: 7.5m; level difference: 0m |
(6) - Heating: indoor temp. 20°CDB; inlet water temperature: 20°C; equivalent piping length: 7.5m; level difference: 0m |
(6) - Heating: indoor temp. 20°CDB; inlet water temperature: 20°C; equivalent piping length: 7.5m; level difference: 0m |
|
(7) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) |
(7) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) |
(7) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) |
(7) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) |
(7) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) |
(7) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) |
(7) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) |
(7) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) |
(7) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) |
(7) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) |
(7) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) |
(7) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) |
(7) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) |
(7) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) |
(7) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) |
(7) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) |
(7) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) |
(7) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) |
|
(8) - Water flow rate for performance testing according to standard rating conditions of EN 14511-2. |
(8) - Water flow rate for performance testing according to standard rating conditions of EN 14511-2. |
(8) - Water flow rate for performance testing according to standard rating conditions of EN 14511-2. |
(8) - Water flow rate for performance testing according to standard rating conditions of EN 14511-2. |
(8) - Water flow rate for performance testing according to standard rating conditions of EN 14511-2. |
(8) - Water flow rate for performance testing according to standard rating conditions of EN 14511-2. |
(8) - Water flow rate for performance testing according to standard rating conditions of EN 14511-2. |
(8) - Water flow rate for performance testing according to standard rating conditions of EN 14511-2. |
(8) - Water flow rate for performance testing according to standard rating conditions of EN 14511-2. |
(8) - Water flow rate for performance testing according to standard rating conditions of EN 14511-2. |
(8) - Water flow rate for performance testing according to standard rating conditions of EN 14511-2. |
(8) - Water flow rate for performance testing according to standard rating conditions of EN 14511-2. |
(8) - Water flow rate for performance testing according to standard rating conditions of EN 14511-2. |
(8) - Water flow rate for performance testing according to standard rating conditions of EN 14511-2. |
(8) - Water flow rate for performance testing according to standard rating conditions of EN 14511-2. |
(8) - Water flow rate for performance testing according to standard rating conditions of EN 14511-2. |
(8) - Water flow rate for performance testing according to standard rating conditions of EN 14511-2. |
(8) - Water flow rate for performance testing according to standard rating conditions of EN 14511-2. |
|
(9) - Sound power level is an absolute value that a sound source generates. |
(9) - Sound power level is an absolute value that a sound source generates. |
(9) - Sound power level is an absolute value that a sound source generates. |
(9) - Sound power level is an absolute value that a sound source generates. |
(9) - Sound power level is an absolute value that a sound source generates. |
(9) - Sound power level is an absolute value that a sound source generates. |
(9) - Sound power level is an absolute value that a sound source generates. |
(9) - Sound power level is an absolute value that a sound source generates. |
(9) - Sound power level is an absolute value that a sound source generates. |
(9) - Sound power level is an absolute value that a sound source generates. |
(9) - Sound power level is an absolute value that a sound source generates. |
(9) - Sound power level is an absolute value that a sound source generates. |
(9) - Sound power level is an absolute value that a sound source generates. |
(9) - Sound power level is an absolute value that a sound source generates. |
(9) - Sound power level is an absolute value that a sound source generates. |
(9) - Sound power level is an absolute value that a sound source generates. |
(9) - Sound power level is an absolute value that a sound source generates. |
(9) - Sound power level is an absolute value that a sound source generates. |
|
(10) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. |
(10) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. |
(10) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. |
(10) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. |
(10) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. |
(10) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. |
(10) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. |
(10) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. |
(10) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. |
(10) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. |
(10) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. |
(10) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. |
(10) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. |
(10) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. |
(10) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. |
(10) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. |
(10) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. |
(10) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. |
|
(11) - In case of heat pump system, gas pipe is not used |
(11) - In case of heat pump system, gas pipe is not used |
(11) - In case of heat pump system, gas pipe is not used |
(11) - In case of heat pump system, gas pipe is not used |
(11) - In case of heat pump system, gas pipe is not used |
(11) - In case of heat pump system, gas pipe is not used |
(11) - In case of heat pump system, gas pipe is not used |
(11) - In case of heat pump system, gas pipe is not used |
(11) - In case of heat pump system, gas pipe is not used |
(11) - In case of heat pump system, gas pipe is not used |
(11) - In case of heat pump system, gas pipe is not used |
(11) - In case of heat pump system, gas pipe is not used |
(11) - In case of heat pump system, gas pipe is not used |
(11) - In case of heat pump system, gas pipe is not used |
(11) - In case of heat pump system, gas pipe is not used |
(11) - In case of heat pump system, gas pipe is not used |
(11) - In case of heat pump system, gas pipe is not used |
(11) - In case of heat pump system, gas pipe is not used |
|
(12) - In case of heat recovery system |
(12) - In case of heat recovery system |
(12) - In case of heat recovery system |
(12) - In case of heat recovery system |
(12) - In case of heat recovery system |
(12) - In case of heat recovery system |
(12) - In case of heat recovery system |
(12) - In case of heat recovery system |
(12) - In case of heat recovery system |
(12) - In case of heat recovery system |
(12) - In case of heat recovery system |
(12) - In case of heat recovery system |
(12) - In case of heat recovery system |
(12) - In case of heat recovery system |
(12) - In case of heat recovery system |
(12) - In case of heat recovery system |
(12) - In case of heat recovery system |
(12) - In case of heat recovery system |
|
(13) - In case of heat pump system |
(13) - In case of heat pump system |
(13) - In case of heat pump system |
(13) - In case of heat pump system |
(13) - In case of heat pump system |
(13) - In case of heat pump system |
(13) - In case of heat pump system |
(13) - In case of heat pump system |
(13) - In case of heat pump system |
(13) - In case of heat pump system |
(13) - In case of heat pump system |
(13) - In case of heat pump system |
(13) - In case of heat pump system |
(13) - In case of heat pump system |
(13) - In case of heat pump system |
(13) - In case of heat pump system |
(13) - In case of heat pump system |
(13) - In case of heat pump system |
|
(14) - Refer to refrigerant pipe selection or installation manual |
(14) - Refer to refrigerant pipe selection or installation manual |
(14) - Refer to refrigerant pipe selection or installation manual |
(14) - Refer to refrigerant pipe selection or installation manual |
(14) - Refer to refrigerant pipe selection or installation manual |
(14) - Refer to refrigerant pipe selection or installation manual |
(14) - Refer to refrigerant pipe selection or installation manual |
(14) - Refer to refrigerant pipe selection or installation manual |
(14) - Refer to refrigerant pipe selection or installation manual |
(14) - Refer to refrigerant pipe selection or installation manual |
(14) - Refer to refrigerant pipe selection or installation manual |
(14) - Refer to refrigerant pipe selection or installation manual |
(14) - Refer to refrigerant pipe selection or installation manual |
(14) - Refer to refrigerant pipe selection or installation manual |
(14) - Refer to refrigerant pipe selection or installation manual |
(14) - Refer to refrigerant pipe selection or installation manual |
(14) - Refer to refrigerant pipe selection or installation manual |
(14) - Refer to refrigerant pipe selection or installation manual |
|
(15) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; inlet water temp. 30°C |
(15) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; inlet water temp. 30°C |
(15) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; inlet water temp. 30°C |
(15) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; inlet water temp. 30°C |
(15) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; inlet water temp. 30°C |
(15) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; inlet water temp. 30°C |
(15) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; inlet water temp. 30°C |
(15) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; inlet water temp. 30°C |
(15) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; inlet water temp. 30°C |
(15) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; inlet water temp. 30°C |
(15) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; inlet water temp. 30°C |
(15) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; inlet water temp. 30°C |
(15) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; inlet water temp. 30°C |
(15) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; inlet water temp. 30°C |
(15) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; inlet water temp. 30°C |
(15) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; inlet water temp. 30°C |
(15) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; inlet water temp. 30°C |
(15) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; inlet water temp. 30°C |
|
(16) - MSC значи максималната струја при стартување на компресорот. Оваа единица користи само компресори со инвертор. Струјата за стартување секогаш е ≤ max. од струјата за работа. |
(16) - MSC значи максималната струја при стартување на компресорот. Оваа единица користи само компресори со инвертор. Струјата за стартување секогаш е ≤ max. од струјата за работа. |
(16) - MSC значи максималната струја при стартување на компресорот. Оваа единица користи само компресори со инвертор. Струјата за стартување секогаш е ≤ max. од струјата за работа. |
(16) - MSC значи максималната струја при стартување на компресорот. Оваа единица користи само компресори со инвертор. Струјата за стартување секогаш е ≤ max. од струјата за работа. |
(16) - MSC значи максималната струја при стартување на компресорот. Оваа единица користи само компресори со инвертор. Струјата за стартување секогаш е ≤ max. од струјата за работа. |
(16) - MSC значи максималната струја при стартување на компресорот. Оваа единица користи само компресори со инвертор. Струјата за стартување секогаш е ≤ max. од струјата за работа. |
(16) - MSC значи максималната струја при стартување на компресорот. Оваа единица користи само компресори со инвертор. Струјата за стартување секогаш е ≤ max. од струјата за работа. |
(16) - MSC значи максималната струја при стартување на компресорот. Оваа единица користи само компресори со инвертор. Струјата за стартување секогаш е ≤ max. од струјата за работа. |
(16) - MSC значи максималната струја при стартување на компресорот. Оваа единица користи само компресори со инвертор. Струјата за стартување секогаш е ≤ max. од струјата за работа. |
(16) - MSC значи максималната струја при стартување на компресорот. Оваа единица користи само компресори со инвертор. Струјата за стартување секогаш е ≤ max. од струјата за работа. |
(16) - MSC значи максималната струја при стартување на компресорот. Оваа единица користи само компресори со инвертор. Струјата за стартување секогаш е ≤ max. од струјата за работа. |
(16) - MSC значи максималната струја при стартување на компресорот. Оваа единица користи само компресори со инвертор. Струјата за стартување секогаш е ≤ max. од струјата за работа. |
(16) - MSC значи максималната струја при стартување на компресорот. Оваа единица користи само компресори со инвертор. Струјата за стартување секогаш е ≤ max. од струјата за работа. |
(16) - MSC значи максималната струја при стартување на компресорот. Оваа единица користи само компресори со инвертор. Струјата за стартување секогаш е ≤ max. од струјата за работа. |
(16) - MSC значи максималната струја при стартување на компресорот. Оваа единица користи само компресори со инвертор. Струјата за стартување секогаш е ≤ max. од струјата за работа. |
(16) - MSC значи максималната струја при стартување на компресорот. Оваа единица користи само компресори со инвертор. Струјата за стартување секогаш е ≤ max. од струјата за работа. |
(16) - MSC значи максималната струја при стартување на компресорот. Оваа единица користи само компресори со инвертор. Струјата за стартување секогаш е ≤ max. од струјата за работа. |
(16) - MSC значи максималната струја при стартување на компресорот. Оваа единица користи само компресори со инвертор. Струјата за стартување секогаш е ≤ max. од струјата за работа. |
|
(17) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value |
(17) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value |
(17) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value |
(17) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value |
(17) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value |
(17) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value |
(17) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value |
(17) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value |
(17) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value |
(17) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value |
(17) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value |
(17) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value |
(17) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value |
(17) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value |
(17) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value |
(17) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value |
(17) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value |
(17) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value |
|
(18) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. |
(18) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. |
(18) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. |
(18) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. |
(18) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. |
(18) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. |
(18) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. |
(18) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. |
(18) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. |
(18) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. |
(18) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. |
(18) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. |
(18) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. |
(18) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. |
(18) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. |
(18) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. |
(18) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. |
(18) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. |
|
(19) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). |
(19) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). |
(19) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). |
(19) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). |
(19) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). |
(19) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). |
(19) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). |
(19) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). |
(19) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). |
(19) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). |
(19) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). |
(19) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). |
(19) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). |
(19) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). |
(19) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). |
(19) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). |
(19) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). |
(19) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). |
|
(20) - TOCA means the total value of each OC set. |
(20) - TOCA means the total value of each OC set. |
(20) - TOCA means the total value of each OC set. |
(20) - TOCA means the total value of each OC set. |
(20) - TOCA means the total value of each OC set. |
(20) - TOCA means the total value of each OC set. |
(20) - TOCA means the total value of each OC set. |
(20) - TOCA means the total value of each OC set. |
(20) - TOCA means the total value of each OC set. |
(20) - TOCA means the total value of each OC set. |
(20) - TOCA means the total value of each OC set. |
(20) - TOCA means the total value of each OC set. |
(20) - TOCA means the total value of each OC set. |
(20) - TOCA means the total value of each OC set. |
(20) - TOCA means the total value of each OC set. |
(20) - TOCA means the total value of each OC set. |
(20) - TOCA means the total value of each OC set. |
(20) - TOCA means the total value of each OC set. |
|
(21) - Maximum allowable voltage range variation between phases is 2%. |
(21) - Maximum allowable voltage range variation between phases is 2%. |
(21) - Maximum allowable voltage range variation between phases is 2%. |
(21) - Maximum allowable voltage range variation between phases is 2%. |
(21) - Maximum allowable voltage range variation between phases is 2%. |
(21) - Maximum allowable voltage range variation between phases is 2%. |
(21) - Maximum allowable voltage range variation between phases is 2%. |
(21) - Maximum allowable voltage range variation between phases is 2%. |
(21) - Maximum allowable voltage range variation between phases is 2%. |
(21) - Maximum allowable voltage range variation between phases is 2%. |
(21) - Maximum allowable voltage range variation between phases is 2%. |
(21) - Maximum allowable voltage range variation between phases is 2%. |
(21) - Maximum allowable voltage range variation between phases is 2%. |
(21) - Maximum allowable voltage range variation between phases is 2%. |
(21) - Maximum allowable voltage range variation between phases is 2%. |
(21) - Maximum allowable voltage range variation between phases is 2%. |
(21) - Maximum allowable voltage range variation between phases is 2%. |
(21) - Maximum allowable voltage range variation between phases is 2%. |
|
(22) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. |
(22) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. |
(22) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. |
(22) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. |
(22) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. |
(22) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. |
(22) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. |
(22) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. |
(22) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. |
(22) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. |
(22) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. |
(22) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. |
(22) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. |
(22) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. |
(22) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. |
(22) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. |
(22) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. |
(22) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. |
|
(23) - Sound values are measured in a semi-anechoic room. |
(23) - Sound values are measured in a semi-anechoic room. |
(23) - Sound values are measured in a semi-anechoic room. |
(23) - Sound values are measured in a semi-anechoic room. |
(23) - Sound values are measured in a semi-anechoic room. |
(23) - Sound values are measured in a semi-anechoic room. |
(23) - Sound values are measured in a semi-anechoic room. |
(23) - Sound values are measured in a semi-anechoic room. |
(23) - Sound values are measured in a semi-anechoic room. |
(23) - Sound values are measured in a semi-anechoic room. |
(23) - Sound values are measured in a semi-anechoic room. |
(23) - Sound values are measured in a semi-anechoic room. |
(23) - Sound values are measured in a semi-anechoic room. |
(23) - Sound values are measured in a semi-anechoic room. |
(23) - Sound values are measured in a semi-anechoic room. |
(23) - Sound values are measured in a semi-anechoic room. |
(23) - Sound values are measured in a semi-anechoic room. |
(23) - Sound values are measured in a semi-anechoic room. |
|
(24) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA |
(24) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA |
(24) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA |
(24) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA |
(24) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA |
(24) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA |
(24) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA |
(24) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA |
(24) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA |
(24) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA |
(24) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA |
(24) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA |
(24) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA |
(24) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA |
(24) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA |
(24) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA |
(24) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA |
(24) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA |
|
(25) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase |
(25) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase |
(25) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase |
(25) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase |
(25) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase |
(25) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase |
(25) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase |
(25) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase |
(25) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase |
(25) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase |
(25) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase |
(25) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase |
(25) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase |
(25) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase |
(25) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase |
(25) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase |
(25) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase |
(25) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase |
|
(26) - Ssc: Short-circuit power |
(26) - Ssc: Short-circuit power |
(26) - Ssc: Short-circuit power |
(26) - Ssc: Short-circuit power |
(26) - Ssc: Short-circuit power |
(26) - Ssc: Short-circuit power |
(26) - Ssc: Short-circuit power |
(26) - Ssc: Short-circuit power |
(26) - Ssc: Short-circuit power |
(26) - Ssc: Short-circuit power |
(26) - Ssc: Short-circuit power |
(26) - Ssc: Short-circuit power |
(26) - Ssc: Short-circuit power |
(26) - Ssc: Short-circuit power |
(26) - Ssc: Short-circuit power |
(26) - Ssc: Short-circuit power |
(26) - Ssc: Short-circuit power |
(26) - Ssc: Short-circuit power |
|
(27) - For detailed contents of standard accessories, see installation/operation manual |
(27) - For detailed contents of standard accessories, see installation/operation manual |
(27) - For detailed contents of standard accessories, see installation/operation manual |
(27) - For detailed contents of standard accessories, see installation/operation manual |
(27) - For detailed contents of standard accessories, see installation/operation manual |
(27) - For detailed contents of standard accessories, see installation/operation manual |
(27) - For detailed contents of standard accessories, see installation/operation manual |
(27) - For detailed contents of standard accessories, see installation/operation manual |
(27) - For detailed contents of standard accessories, see installation/operation manual |
(27) - For detailed contents of standard accessories, see installation/operation manual |
(27) - For detailed contents of standard accessories, see installation/operation manual |
(27) - For detailed contents of standard accessories, see installation/operation manual |
(27) - For detailed contents of standard accessories, see installation/operation manual |
(27) - For detailed contents of standard accessories, see installation/operation manual |
(27) - For detailed contents of standard accessories, see installation/operation manual |
(27) - For detailed contents of standard accessories, see installation/operation manual |
(27) - For detailed contents of standard accessories, see installation/operation manual |
(27) - For detailed contents of standard accessories, see installation/operation manual |
|
(28) - Multi combination (10~54HP) data is corresponding with the standard multi combination |
(28) - Multi combination (10~54HP) data is corresponding with the standard multi combination |
(28) - Multi combination (10~54HP) data is corresponding with the standard multi combination |
(28) - Multi combination (10~54HP) data is corresponding with the standard multi combination |
(28) - Multi combination (10~54HP) data is corresponding with the standard multi combination |
(28) - Multi combination (10~54HP) data is corresponding with the standard multi combination |
(28) - Multi combination (10~54HP) data is corresponding with the standard multi combination |
(28) - Multi combination (10~54HP) data is corresponding with the standard multi combination |
(28) - Multi combination (10~54HP) data is corresponding with the standard multi combination |
(28) - Multi combination (10~54HP) data is corresponding with the standard multi combination |
(28) - Multi combination (10~54HP) data is corresponding with the standard multi combination |
(28) - Multi combination (10~54HP) data is corresponding with the standard multi combination |
(28) - Multi combination (10~54HP) data is corresponding with the standard multi combination |
(28) - Multi combination (10~54HP) data is corresponding with the standard multi combination |
(28) - Multi combination (10~54HP) data is corresponding with the standard multi combination |
(28) - Multi combination (10~54HP) data is corresponding with the standard multi combination |
(28) - Multi combination (10~54HP) data is corresponding with the standard multi combination |
(28) - Multi combination (10~54HP) data is corresponding with the standard multi combination |