Табела со спецификации за ELBX-E9W

ELBX12EF9W ELBX12EJ9W
Куќиште Боја   White + Black White + Black
  Материјал   Resin, sheet metal Resin, sheet metal
Димензии Единица Висина mm 840 840
    Ширина mm 440 440
    Длабочина mm 390 390
Тежина Единица kg 48.5 48.5
PED Категорија   Category II Category II
Sound power level Nom. dBA 44.0 (3) 44.0 (3)
Sound pressure level Nom. dBA 30.0 (4) 30.0 (4)
Operation range Heating Water side Min. °C 15 (5) 20 (5)
      Max. °C 65 (5) 65 (5)
  Cooling Ambient Min. °CDB 10 (5) 10 (5)
    Water side Min. °C 5 (5) 5 (5)
      Max. °C 22 (5) 22 (5)
Напојување со струја Име   See note 6 See note 6
Electric heater Power supply Name   9W 9W
    Phase   3~ 3~
    Frequency Hz 50 50
    Voltage V 400 400
  Recommended fuses A 20.000 (7) 20.000 (7)
Notes (1) - Работниот простор е проширен за да се намали брзината на протокот, во зависност од режимот на работа - погледнете ја кривата ESP. (1) - Работниот простор е проширен за да се намали брзината на протокот, во зависност од режимот на работа - погледнете ја кривата ESP.
  (2) - Excluding the water volume in the unit. This volume will guarantee suficient defrost energy for all applications, however, this volume can be multiplied by 0,66 if the heating sepoint is ≥ 45° C (eg. Fan coils) (2) - Excluding the water volume in the unit. This volume will guarantee suficient defrost energy for all applications, however, this volume can be multiplied by 0,66 if the heating sepoint is ≥ 45° C (eg. Fan coils)
  (3) - Measured with a pressure drop of 10 kPa in the heating system at an operating condition of leaving water 47-55°C in a room with an ambient of 20°C. DB/WB 7°C/6°. (3) - Measured with a pressure drop of 10 kPa in the heating system at an operating condition of leaving water 47-55°C in a room with an ambient of 20°C. DB/WB 7°C/6°.
  (4) - Sound values are measured in a semi-anechoic room. Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. Sound power level is an absolute value that a so (4) - Sound values are measured in a semi-anechoic room. Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. Sound power level is an absolute value that a so
  (5) - For more details, see operation range drawing (5) - For more details, see operation range drawing
  (6) - Above mentioned power supply of the hydrobox is for the backup heater only. The switch box and the pump of the hydrobox are supplied via the outdoor unit. The optional domestic hot water tank has a separate power supply. (6) - Above mentioned power supply of the hydrobox is for the backup heater only. The switch box and the pump of the hydrobox are supplied via the outdoor unit. The optional domestic hot water tank has a separate power supply.
  (7) - 4 pole 20 A curve 400V tripping class C (refer to wiring diagram) (7) - 4 pole 20 A curve 400V tripping class C (refer to wiring diagram)