|
LREQ5B7Y1 |
LREQ6B7Y1 |
LREQ8B7Y1 |
LREQ10B7Y1 |
LREQ12B7Y1 |
LREQ15B7Y1 |
LREQ20B7Y1 |
LREQ30B7Y1 |
LREQ40B7Y1 |
Refrigerating capacity |
Low temperature |
Nom. |
kW |
5.51 (2) |
6.51 (2) |
8.33 (2) |
10.0 (2) |
10.7 (2) |
13.9 (2) |
15.4 (2) |
27.8 |
29.6 |
|
Medium temperature |
Nom. |
kW |
12.5 (1) |
15.2 (1) |
19.8 (1) |
23.8 (1) |
26.5 (1) |
33.9 (1) |
37.9 (1) |
67.8 (3) |
75.8 (3) |
Power input |
Low temperature |
Nom. |
kW |
4.65 (2) |
5.88 (2) |
7.72 (2) |
9.27 (2) |
9.89 (2) |
12.8 (2) |
14.1 (2) |
25.6 |
27.6 |
|
Medium temperature |
Nom. |
kW |
5.10 (1) |
6.56 (1) |
8.76 (1) |
10.6 (1) |
12.0 (1) |
15.2 (1) |
17.0 (1) |
30.4 |
34.0 |
Annual electricity consumption Q |
R-410A |
Te -10°C |
kWh/a |
19,907 |
24,681 |
33,483 |
42,794 |
46,377 |
61,683 |
72,030 |
|
|
|
|
Te -35°C |
kWh/a |
22,805 |
27,453 |
33,817 |
39,747 |
44,363 |
61,090 |
67,325 |
|
|
Seasonal energy performance ratio SEPR |
R-410A |
Te -10°C |
|
3.86 |
3.79 |
3.64 |
3.42 |
3.51 |
3.38 |
3.23 |
|
|
|
|
Te -35°C |
|
1.80 |
1.77 |
1.84 |
1.88 |
1.80 |
1.70 |
1.70 |
|
|
Parameters at full load and ambient temp. 32°C (Point A) |
R-410A |
Te -10°C |
Rated cooling capacity (PA) |
kW |
12.50 |
15.20 |
19.80 |
23.80 |
26.50 |
33.90 |
37.90 |
|
|
|
|
|
Rated power input (DA) |
kW |
5.10 |
6.56 |
8.76 |
10.60 |
12.00 |
15.20 |
17.00 |
|
|
|
|
|
Rated COP (COPA) |
|
2.45 |
2.32 |
2.26 |
2.25 |
2.21 |
2.23 |
2.23 |
|
|
|
|
Te -35°C |
Rated cooling capacity (PA) |
kW |
5.51 |
6.51 |
8.33 |
10.00 |
10.70 |
13.90 |
15.40 |
|
|
|
|
|
Rated power input (DA) |
kW |
4.65 |
5.88 |
7.72 |
9.27 |
9.89 |
12.80 |
14.10 |
|
|
|
|
|
Rated COP (COPA) |
|
1.18 |
1.11 |
1.08 |
1.08 |
1.08 |
1.09 |
1.09 |
|
|
Parameters at full load and ambient temp. 43°C |
R-410A |
Te -10°C |
Cooling capacity (P3) |
kW |
10.50 |
12.50 |
16.20 |
18.50 |
20.10 |
26.10 |
30.80 |
|
|
|
|
|
Power input (D3) |
kW |
6.83 |
7.97 |
11.60 |
12.70 |
13.70 |
17.90 |
20.40 |
|
|
|
|
|
Declared COP (COP3) |
|
1.54 |
1.57 |
1.40 |
1.46 |
1.47 |
1.46 |
1.51 |
|
|
|
|
Te -35°C |
Cooling capacity (P3) |
kW |
4.51 |
5.15 |
6.58 |
7.67 |
8.33 |
11.20 |
12.40 |
|
|
|
|
|
Power input (D3) |
kW |
5.96 |
6.99 |
9.65 |
10.90 |
11.70 |
15.70 |
16.80 |
|
|
|
|
|
Declared COP (COP3) |
|
0.76 |
0.74 |
0.68 |
0.70 |
0.71 |
0.71 |
0.74 |
|
|
Casing |
Colour |
|
Ivory white (Munsell code: 5Y7.5/1) |
Ivory white (Munsell code: 5Y7.5/1) |
Ivory white (Munsell code: 5Y7.5/1) |
Ivory white (Munsell code: 5Y7.5/1) |
Ivory white (Munsell code: 5Y7.5/1) |
Ivory white (Munsell code: 5Y7.5/1) |
Ivory white (Munsell code: 5Y7.5/1) |
|
|
Dimensions |
Unit |
Height |
mm |
1,680 |
1,680 |
1,680 |
1,680 |
1,680 |
1,680 |
1,680 |
|
|
|
|
Width |
mm |
635 |
635 |
930 |
930 |
930 |
1,240 |
1,240 |
|
|
|
|
Depth |
mm |
765 |
765 |
765 |
765 |
765 |
765 |
765 |
|
|
Weight |
Unit |
kg |
166 |
166 |
242 |
242 |
242 |
331 |
337 |
|
|
Compressor 2 |
Type |
|
|
Hermetically sealed scroll compressor |
Hermetically sealed scroll compressor |
Hermetically sealed scroll compressor |
Hermetically sealed scroll compressor |
Hermetically sealed scroll compressor |
|
|
Fan |
Type |
|
Propeller fan |
Propeller fan |
Propeller fan |
Propeller fan |
Propeller fan |
Propeller fan |
Propeller fan |
|
|
|
Quantity |
|
1 |
1 |
1 |
1 |
1 |
2 |
2 |
|
|
|
Air flow rate |
Cooling |
Nom. |
m³/min |
95 |
102 |
171 |
179 |
191 |
230 |
240 |
|
|
Fan motor |
Output |
W |
350 |
350 |
750 |
750 |
750 |
350 |
750 |
|
|
|
Drive |
|
Direct drive |
Direct drive |
Direct drive |
Direct drive |
Direct drive |
Direct drive |
Direct drive |
|
|
Fan motor 2 |
Output |
W |
|
|
|
|
|
350 |
750 |
|
|
Heat exchanger |
Type |
|
Cross fin coil |
Cross fin coil |
Cross fin coil |
Cross fin coil |
Cross fin coil |
Cross fin coil |
Cross fin coil |
|
|
Operation range |
Ambient temperature |
Max. |
°C |
43 |
43 |
43 |
43 |
43 |
43 |
43 |
|
|
|
|
Min. |
°C |
-20 |
-20 |
-20 |
-20 |
-20 |
-20 |
-20 |
|
|
|
Evaporator |
Cooling |
Max. |
°CDB |
10 |
10 |
10 |
10 |
10 |
10 |
10 |
|
|
|
|
|
Min. |
°CDB |
-45 |
-45 |
-45 |
-45 |
-45 |
-45 |
-45 |
|
|
Refrigerant |
Type |
|
R-410A |
R-410A |
R-410A |
R-410A |
R-410A |
R-410A |
R-410A |
|
|
|
GWP |
|
2,087.5 |
2,087.5 |
2,087.5 |
2,087.5 |
2,087.5 |
2,087.5 |
2,087.5 |
|
|
|
Charge |
kg |
5.2 |
5.2 |
7.9 |
7.9 |
7.9 |
11.5 |
11.5 |
|
|
|
Charge |
TCO2Eq |
10.9 |
10.9 |
16.5 |
16.5 |
16.5 |
24.0 |
24.0 |
|
|
Piping connections |
Gas |
50~130m |
|
ø 22.2 C1220T (Brazing connection) |
ø 22.2 C1220T (Brazing connection) |
ø 28.6 C1220T (Brazing connection) |
ø 28.6 C1220T (Brazing connection) |
ø 28.6 C1220T (Brazing connection) |
ø 34.9 C1220T (Brazing connection) |
ø 34.9 C1220T (Brazing connection) |
ø 41.28 C1220T (Brazing connection) |
ø 41.28 C1220T (Brazing connection) |
|
|
50m or less |
|
ø 22.2 C1220T (Brazing connection) |
ø 22.2 C1220T (Brazing connection) |
ø 28.6 C1220T (Brazing connection) |
ø 28.6 C1220T (Brazing connection) |
ø 28.6 C1220T (Brazing connection) |
ø 34.9 C1220T (Brazing connection) |
ø 34.9 C1220T (Brazing connection) |
ø 41.28 C1220T (Brazing connection) |
ø 41.28 C1220T (Brazing connection) |
|
Liquid |
50~130m |
|
ø 9.5 C1220T (Brazing connection) |
ø 9.5 C1220T (Brazing connection) |
ø 12.7 C1220T (Brazing connection) |
ø 12.7 C1220T (Brazing connection) |
ø 12.7 C1220T (Brazing connection) |
ø 12.7 C1220T (Brazing connection) |
ø 12.7 C1220T (Brazing connection) |
ø 19.05 C1220T (Brazing connection) |
ø 19.05 C1220T (Brazing connection) |
|
|
50m or less |
|
ø 9.5 C1220T (Brazing connection) |
ø 9.5 C1220T (Brazing connection) |
ø 9.5 C1220T (Brazing connection) |
ø 9.5 C1220T (Brazing connection) |
ø 12.7 C1220T (Brazing connection) |
ø 12.7 C1220T (Brazing connection) |
ø 12.7 C1220T (Brazing connection) |
ø 19.05 C1220T (Brazing connection) |
ø 19.05 C1220T (Brazing connection) |
Power supply |
Phase |
|
3~ |
3~ |
3~ |
3~ |
3~ |
3~ |
3~ |
|
|
|
Frequency |
Hz |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
|
|
|
Voltage |
V |
380-415 |
380-415 |
380-415 |
380-415 |
380-415 |
380-415 |
380-415 |
|
|
Current |
Nominal running current (RLA) - 50Hz |
Compressor 1 |
Cooling |
A |
7.1 |
9.2 |
5.3 |
7.4 |
9.8 |
7.0 |
9.5 |
|
|
|
|
Compressor 2 |
Cooling |
A |
|
|
7.5 |
7.9 |
8.3 |
8.2 |
8.4 |
|
|
|
|
Compressor 3 |
Cooling |
A |
|
|
|
|
|
8.2 |
8.4 |
|
|
Notes |
(1) - Cooling: evaporating temp. -10°C; outdoor temp. 32°C; suction SH10°C |
(1) - Cooling: evaporating temp. -10°C; outdoor temp. 32°C; suction SH10°C |
(1) - Cooling: evaporating temp. -10°C; outdoor temp. 32°C; suction SH10°C |
(1) - Cooling: evaporating temp. -10°C; outdoor temp. 32°C; suction SH10°C |
(1) - Cooling: evaporating temp. -10°C; outdoor temp. 32°C; suction SH10°C |
(1) - Cooling: evaporating temp. -10°C; outdoor temp. 32°C; suction SH10°C |
(1) - Cooling: evaporating temp. -10°C; outdoor temp. 32°C; suction SH10°C |
(1) - When target evaporating temperature is -20°C or lower, there is the possibility to add the refrigerant oil. If the refrigerant oil is added, the target evaporating temperature can not change to -20°C or higher. |
(1) - When target evaporating temperature is -20°C or lower, there is the possibility to add the refrigerant oil. If the refrigerant oil is added, the target evaporating temperature can not change to -20°C or higher. |
|
(2) - Cooling: evaporating temp. -35°C; outdoor temp. 32°C; suction SH10°C |
(2) - Cooling: evaporating temp. -35°C; outdoor temp. 32°C; suction SH10°C |
(2) - Cooling: evaporating temp. -35°C; outdoor temp. 32°C; suction SH10°C |
(2) - Cooling: evaporating temp. -35°C; outdoor temp. 32°C; suction SH10°C |
(2) - Cooling: evaporating temp. -35°C; outdoor temp. 32°C; suction SH10°C |
(2) - Cooling: evaporating temp. -35°C; outdoor temp. 32°C; suction SH10°C |
(2) - Cooling: evaporating temp. -35°C; outdoor temp. 32°C; suction SH10°C |
(2) - In the usage environment which outdoor temperature becomes lower than -10°C, installation of windbreak board or snowbreak hood is needed. For details, see the service manual. |
(2) - In the usage environment which outdoor temperature becomes lower than -10°C, installation of windbreak board or snowbreak hood is needed. For details, see the service manual. |
|
(3) - Sound pressure data: measured at 1m in front of unit, at 1.5m height |
(3) - Sound pressure data: measured at 1m in front of unit, at 1.5m height |
(3) - Sound pressure data: measured at 1m in front of unit, at 1.5m height |
(3) - Sound pressure data: measured at 1m in front of unit, at 1.5m height |
(3) - Sound pressure data: measured at 1m in front of unit, at 1.5m height |
(3) - Sound pressure data: measured at 1m in front of unit, at 1.5m height |
(3) - Sound pressure data: measured at 1m in front of unit, at 1.5m height |
(3) - Operation conditions of outside unit: evaporating temperature = -10°C, outdoor temperature +32°C, Suction SH 10K |
(3) - Operation conditions of outside unit: evaporating temperature = -10°C, outdoor temperature +32°C, Suction SH 10K |
|
(4) - RLA is based on following conditions: outdoor temp. 32°CDB; suction SH 10°C; saturated temperature equivalent to suction pressure -10°C |
(4) - RLA is based on following conditions: outdoor temp. 32°CDB; suction SH 10°C; saturated temperature equivalent to suction pressure -10°C |
(4) - RLA is based on following conditions: outdoor temp. 32°CDB; suction SH 10°C; saturated temperature equivalent to suction pressure -10°C |
(4) - RLA is based on following conditions: outdoor temp. 32°CDB; suction SH 10°C; saturated temperature equivalent to suction pressure -10°C |
(4) - RLA is based on following conditions: outdoor temp. 32°CDB; suction SH 10°C; saturated temperature equivalent to suction pressure -10°C |
(4) - RLA is based on following conditions: outdoor temp. 32°CDB; suction SH 10°C; saturated temperature equivalent to suction pressure -10°C |
(4) - RLA is based on following conditions: outdoor temp. 32°CDB; suction SH 10°C; saturated temperature equivalent to suction pressure -10°C |
(4) - Have to use the Branch Pipe Kit (EKHRQZM) to divide a suction pipe between the outdoor units. |
(4) - Have to use the Branch Pipe Kit (EKHRQZM) to divide a suction pipe between the outdoor units. |
|
(5) - TOCA means the total value of each OC set. |
(5) - TOCA means the total value of each OC set. |
(5) - TOCA means the total value of each OC set. |
(5) - TOCA means the total value of each OC set. |
(5) - TOCA means the total value of each OC set. |
(5) - TOCA means the total value of each OC set. |
(5) - TOCA means the total value of each OC set. |
(5) - Have to use the refrigerant oil of DAIKIN service parts. (1 liter can: parts no, 5004333) |
(5) - Have to use the refrigerant oil of DAIKIN service parts. (1 liter can: parts no, 5004333) |
|
(6) - MSC means the maximum current during start up of the compressor |
(6) - MSC means the maximum current during start up of the compressor |
(6) - MSC means the maximum current during start up of the compressor |
(6) - MSC means the maximum current during start up of the compressor |
(6) - MSC means the maximum current during start up of the compressor |
(6) - MSC means the maximum current during start up of the compressor |
(6) - MSC means the maximum current during start up of the compressor |
(6) - The other restricions refer the Operation Condition (3D085617). |
(6) - The other restricions refer the Operation Condition (3D085617). |
|
(7) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. |
(7) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. |
(7) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. |
(7) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. |
(7) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. |
(7) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. |
(7) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. |
(7) - RLA is based on the following conditions: outdoor temperature: 32°C; Suction SH. 10K; Evaporating temperature -10°C. |
(7) - RLA is based on the following conditions: outdoor temperature: 32°C; Suction SH. 10K; Evaporating temperature -10°C. |
|
(8) - Maximum allowable voltage range variation between phases is 2%. |
(8) - Maximum allowable voltage range variation between phases is 2%. |
(8) - Maximum allowable voltage range variation between phases is 2%. |
(8) - Maximum allowable voltage range variation between phases is 2%. |
(8) - Maximum allowable voltage range variation between phases is 2%. |
(8) - Maximum allowable voltage range variation between phases is 2%. |
(8) - Maximum allowable voltage range variation between phases is 2%. |
(8) - TOCA means the total value of each OC set. |
(8) - TOCA means the total value of each OC set. |
|
(9) - Select wire size based on the larger value of MCA or TOCA |
(9) - Select wire size based on the larger value of MCA or TOCA |
(9) - Select wire size based on the larger value of MCA or TOCA |
(9) - Select wire size based on the larger value of MCA or TOCA |
(9) - Select wire size based on the larger value of MCA or TOCA |
(9) - Select wire size based on the larger value of MCA or TOCA |
(9) - Select wire size based on the larger value of MCA or TOCA |
(9) - MSC means the maximum current during start up of the compressor |
(9) - MSC means the maximum current during start up of the compressor |
|
(10) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). |
(10) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). |
(10) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). |
(10) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). |
(10) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). |
(10) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). |
(10) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). |
(10) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. |
(10) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. |
|
(11) - Minimum Ssc (=Short-circuit power) value: Equipment complying with EN 61000-3-2 |
(11) - Minimum Ssc (=Short-circuit power) value: Equipment complying with EN 61000-3-2 |
(11) - Minimum Ssc (=Short-circuit power) value: Equipment complying with EN 61000-3-2 |
(11) - Minimum Ssc (=Short-circuit power) value: Equipment complying with EN 61000-3-2 |
(11) - Minimum Ssc (=Short-circuit power) value: Equipment complying with EN 61000-3-2 |
(11) - Minimum Ssc (=Short-circuit power) value: Equipment complying with EN 61000-3-2 |
(11) - Minimum Ssc (=Short-circuit power) value: Equipment complying with EN 61000-3-2 |
(11) - Maximum allowable voltage range variation between phases is 2%. |
(11) - Maximum allowable voltage range variation between phases is 2%. |
|
(12) - Compressor 1 |
(12) - Compressor 1 |
(12) - Compressor 1 |
(12) - Compressor 1 |
(12) - Compressor 1 |
(12) - Compressor 1 |
(12) - Compressor 1 |
(12) - Select wire size based on the larger value of MCA or TOCA |
(12) - Select wire size based on the larger value of MCA or TOCA |
|
(13) - Compressor 2 |
(13) - Compressor 2 |
(13) - Compressor 2 |
(13) - Compressor 2 |
(13) - Compressor 2 |
(13) - Compressor 2 |
(13) - Compressor 2 |
(13) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). |
(13) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). |
|
(14) - Compressor 2 and 3 |
(14) - Compressor 2 and 3 |
(14) - Compressor 2 and 3 |
(14) - Compressor 2 and 3 |
(14) - Compressor 2 and 3 |
(14) - Compressor 2 and 3 |
(14) - Compressor 2 and 3 |
(14) - Compressor 2 and 3 |
(14) - Compressor 2 and 3 |
|
(15) - Factory charge of unit |
(15) - Factory charge of unit |
(15) - Factory charge of unit |
(15) - Factory charge of unit |
(15) - Factory charge of unit |
(15) - Factory charge of unit |
(15) - Factory charge of unit |
|
|
|
(16) - Contains fluorinated greenhouse gases |
(16) - Contains fluorinated greenhouse gases |
(16) - Contains fluorinated greenhouse gases |
(16) - Contains fluorinated greenhouse gases |
(16) - Contains fluorinated greenhouse gases |
(16) - Contains fluorinated greenhouse gases |
(16) - Contains fluorinated greenhouse gases |
|
|
|
(17) - Ecodesign Regulation: (EU) 2015/1095 |
(17) - Ecodesign Regulation: (EU) 2015/1095 |
(17) - Ecodesign Regulation: (EU) 2015/1095 |
(17) - Ecodesign Regulation: (EU) 2015/1095 |
(17) - Ecodesign Regulation: (EU) 2015/1095 |
(17) - Ecodesign Regulation: (EU) 2015/1095 |
(17) - Ecodesign Regulation: (EU) 2015/1095 |
|
|