FBA100A2VEB / RZQG71L8Y1B FBA140A2VEB / RZQG140L7Y1B FBA71A2VEB / RZQG71L8Y1B FBA140A2VEB / RZQG100L8Y1B FBA100A2VEB / RZQG100L8Y1B FBA140A2VEB / RZQG125L8Y1B FBA125A2VEB / RZQG125L8Y1B
Cooling capacity Nom. kW   13.4 (1) 6.80 (1)   9.50 (1)   12.0 (1)
Heating capacity Nom. kW   15.5 (2) 7.50 (2)   10.8 (2)   13.5 (2)
Nominal efficiency EER   2.68 (3) 3.60 (3)   3.81 (3)   3.31 (3)
  COP   3.60 (3) 4.01 (3)   4.41 (3)   3.90 (3)
  Annual energy consumption kWh     944   1,247 (0.000)   1,813 (0.000)
  Energy labeling Directive Cooling     A   A   A
    Heating     A   A   A
Space cooling Capacity Pdesign kW     6.80        
  Annual energy consumption kWh/a     386        
Space heating (Average climate) Capacity Pdesign kW     6.00        
  Annual energy consumption kWh/a     1,949        
Pto (Thermostat off) W 3.0     4.0   4.0  
Notes   Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m   Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m   Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m
    Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m   Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m   Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m
    EER/COP according to Eurovent 2012, for use outside EU only (3) - EER/COP according to Eurovent 2012, for use outside EU only   EER/COP according to Eurovent 2012, for use outside EU only   EER/COP according to Eurovent 2012, for use outside EU only
Space cooling Energy efficiency class       A++        
  SEER       6.16        
Space heating (Average climate) Energy efficiency class       A+        
  SCOP/A       4.31